Unless otherwise specified diffusers will be supplied with standard finish and fixings.
Model DP-DFP Technical Data
Supply Performance Data
Model DP-DFP(1 - 4)-0(-R). Overall size to suit a 600mm square ceiling grid with a 300mm diameter neck.
| Volume l/s | 150 | 200 | 250 | 300 | 350 |
| Neck Velocity m/s | 2.1 | 2.9 | 3.6 | 4.3 | 5.0 |
| Total Pressure Pa | 5 | 10 | 16 | 22 | 28 |
| Sound Power NRLW | 24 | 32 | 38 | 44 | 48 |
| Throw A metre | 1.1 | 2.0 | 2.4 | 2.9 | 3.4 |
| Throw B metre | 1.8 | 2.4 | 2.8 | 3.4 | 4.4 |
| Throw C metre | 2.2 | 3.1 | 4.3 | 5.6 | 6.8 |
Throws are to a terminal velocity of 0.5m/s.
For DP-DFP(1 - 4)(-R) with 450mm square neck: - Throw x 0.7; - Total Pressure x 0.7; Sound Power Level deduct 7NR.For supply cooling applications we do not recommend an effective neck velocity below 1.0 m/s.
|
|
Exhaust Performance Data
Model DP-DFPE - 0. To suit 600mm square ceiling grid with 300mm diameter neck.
| Volume l/s | 150 | 200 | 250 | 300 | 350 | 400 |
| Neck Velocity m/s | 2.1 | 2.9 | 3.6 | 4.3 | 5.0 | 5.7 |
| Total Pressure Pa | 3 | 6 | 12 | 18 | 23 | 27 |
| Sound Power NRLW | --- | 23 | 29 | 35 | 43 | 47 |
Model DP-DFPE - 0. To suit 600mm square ceiling grid with 450mm square neck.
| Volume l/s | 150 | 250 | 350 | 450 | 550 | 650 |
| Neck Velocity m/s | 0.75 | 1.25 | 1.75 | 2.25 | 2.75 | 3.25 |
| Total Pressure Pa | -- | 3 | 5 | 10 | 16 | 25 |
| Sound Power NRLW | --- | -- | 23 | 29 | 36 | 42 |
Sound power levels are given. For most applications 4NR may be subtracted to allow for absorbtion.
| Our
Mission Air Diffusion as part of Ruskin is committed to leading the HVAC industry with innovative air control products and unrivaled quality that exceed customer expectations through the continuous pursuit of excellence. |
Home | Links | Products | Catalogues | Contact Copyright © 2003. Air Diffusion. All Rights Reserved Minimum system requirements | Legal |
|